On each computer running Server processes, copy:

  • the whole %ProgramData%\Telecontrol\SCADA Server folder — each process has its own folder in it, holding its parameter file, databases and logs, and the license file license.json sits beside them;
  • the C:\Program Files\Telecontrol SCADA\data\Certificates folder — the Server certificate and its private key, and on the central computer the ca subfolder as well — the site certificate authority with its ca_key.pem key. Without it every other computer must join again after a restore (see A new certificate authority). Keep the copy of the keys as safe as the passwords.

On Linux copy the whole /var/lib/scada folder and the /opt/telecontrol-scada/data/Certificates folder, with the processes stopped by sudo /opt/telecontrol-scada/bin/scada-setup stop. /var/lib/scada also holds the password file secrets/service-secrets.env, which keeps the svc and root passwords in plain text: keep the copy where only root can read it, or leave that file out. The services do not start without it, and start does not create it: if the copy has no secrets folder, keep the existing one when restoring, or run apply with the passwords instead of start (see Restore).

Copy only with this computer’s processes stopped: a copy of the files of running databases may be inconsistent. From an elevated command prompt:

"C:\Program Files\Telecontrol SCADA\bin\scada-setup.exe" stop
rem copy %ProgramData%\Telecontrol\SCADA Server
rem and C:\Program Files\Telecontrol SCADA\data\Certificates
"C:\Program Files\Telecontrol SCADA\bin\scada-setup.exe" start --tiers <this computer's processes>

A restore also needs the svc password, the root password, and the computer’s parameters — the --tiers, --central, --advertise, --license, the central computer’s fingerprint and the other options, if given, that scada-setup apply was run with on it. Some of them are in the copied parameter files of the processes, and on Linux the copy also holds secrets/service-secrets.env with the passwords, but the backup does not give them in a form apply can reuse — keep the written record of the options and passwords separately.

Configuration backup

The configuration is an SQLite database in the config\Configuration folder of scada-config; the other processes read it from there. The filestore\Configuration folder holds only the svc service account.

For PostgreSQL, use the standard PostgreSQL backup tools such as pg_dump.

History backup

The historical databases are in historian\History, and the schematic files in filestore\FileSystem.

Versions 2.5 and earlier kept this data in the Configuration, History and FileSystem folders directly under %ProgramData%\Telecontrol\SCADA Server. After upgrading from version 2.5 those folders stay where they are, but the 2.6 processes no longer use them.

Restore

Run the scada-setup commands by their full path from an elevated command prompt.

On the same computer:

  1. Stop the processes: scada-setup stop.
  2. Put the %ProgramData%\Telecontrol\SCADA Server folder (and the Certificates folder, if it is gone, then restrict access to the key file with the icacls command given below in step 3 for a new computer) back from the backup.
  3. Run scada-setup apply with the same computer’s parameters and the svc and root passwords (see Re-running apply). The restored folder takes the permissions of %ProgramData%, which let any user of the computer read it; apply closes it to other users again and starts the services, while scada-setup start does not.
  4. Check the result: scada-setup status.

On a new or rebuilt computer:

  1. Install the package of the same version as the backup.
  2. Put the %ProgramData%\Telecontrol\SCADA Server folder back from the backup.
  3. If the computer’s name is the same, put the C:\Program Files\Telecontrol SCADA\data\Certificates folder back too, then restrict access to the key file (a copied file takes the folder’s permissions):

    icacls "C:\Program Files\Telecontrol SCADA\data\Certificates\ServerPrivateKey.pem" /inheritance:r /grant:r *S-1-5-18:F *S-1-5-32-544:F
    

    If the computer’s name is different, do not put ServerCertificate.pem and ServerPrivateKey.pem back from the Certificates folder (or delete them): the old certificate names the former computer name, and apply creates a new pair only when neither of the two files exists. Put the central computer’s ca subfolder back in any case — otherwise apply creates a new certificate authority and the other computers have to join again (see A new certificate authority). On a computer without scada-config, give apply in step 4 --central-fingerprint too, to get a new certificate from the certificate authority. Take the fingerprint from scada-setup status on the central computer now, not from the recorded parameters: it differs once the central computer’s certificate has been renewed.

  4. Run scada-setup apply with the same computer’s parameters as before, the same svc password, and the root password. The svc password is stored in the restored databases, and with a different one the processes cannot connect to each other. apply registers and starts the services, and keeps the restored databases and certificate. If the site’s other computers name this one in --central by an address that has changed, run apply there with the new address. If this computer runs protocol processes, was set up with --advertise and its address changed, give --advertise the new address.
  5. Create the inbound firewall rules again — the backup does not contain them (see Network preparation). If the address of this computer changed, also correct the remoteip lists of the rules on the site’s other Server computers.
  6. If this is the central computer and its address or name changed, enter the new one in the Server field of the login dialog of each Client (see Client login).
  7. Check the result: scada-setup status.

With a new certificate, third-party OPC UA clients that trusted the old one have to be set up again.

On Linux the folders are the ones in Backup — /var/lib/scada and /opt/telecontrol-scada/data/Certificates — and the commands are sudo /opt/telecontrol-scada/bin/scada-setup …; the icacls step is not needed. Files put back as root (with cp -r, say) belong to root, but scada-setup start gives them back to the scada account and closes the process folders to other users again before it starts the services, so on the same computer scada-setup start is enough instead of step 3 while the secrets folder is in place (otherwise run apply with the passwords); on a new computer run apply as in the steps above (“On a new or rebuilt computer”). If start reports that the scada account does not exist, the system was reinstalled — restore with the new-computer steps.